OWTS Cable PD Fault Locator Oscillating Wave Test System for Locating Partial Discharge Locations in Cables
* Poor installation
* Failures due to inappropriate laying
* Weak spots in cable accessories or
* Deterioration of cable insulation due to aging It allows much more than a simple go or no-go decision.
DAC testing is an advanced maintenance tool which supports asset management and grid operation as well.
* Sound withstand test method with test voltages representing operational stresses
* Sensitive PD measurement and location in complete cable systems (insulation and accessories)
* Assessment of cable aging status in comparison with other cables based on dissipation factor estimation.
On-site DAC voltage test in combination with non-destructive PD and loss factor measurements is unique and fundamental for reliable service of newly installed, repaired or service-aged cable systems.
The M30 series is an integrated partial discharge localization system, mainly used for partial discharge diagnosis of medium voltage cables. The M30 series is an integrated partial discharge localization system, mainly used for partial discharge diagnosis of medium voltage cables. The system tests a damped AC voltage (DAC) at frequencies from 20Hz to 1000Hz. The damping AC voltage generated by the system during the testing process can reach up to 30kV, and is combined with advanced system hardware and system software for diagnosis.
mainly include:
- The latest transistor technology and laser control technology, such as high voltage transistor switches;
- Electronic components, digital signal processing, such as high voltage transistor switches, high voltage sources;
- Digital signal processor and filter, data acquisition device A/D converter not less than 14Bit
- All-in-one software, compatible with data from other similar manufacturers, and automatically export reports
The high-voltage unit can generate oscillating wave high-voltage signals, and the high-voltage generator can generate any value of high voltage of 0-30kV; the partial discharge test device for the distance positioning of partial discharge signals without blind spots, without blind spots, can perform partial discharge positioning for cables below 250m; 1 laptop computer for control; operating software (Chinese/German/English version); external safety control unit; analysis software (Chinese/German/English version); a 7.5-meter high-voltage connection line without partial discharge, and has an anti-drop safety design ; Power line, grounding line, check line, emergency stop line; PD under the highest voltage of the system is less than 1pC.
Unlimited installation of PD analysis software, which can be installed and analyzed on any computer, compatible with data analysis of various similar manufacturers, and has built-in TDR calibration test function, including ultra-low frequency VLF function, double-ended measurement and analysis function, can choose the analysis phase interval, test report One-click automatic generation, after the test is completed and the test report is automatically generated.
For further information on Weshine's Service Solutions, contact our 24/7 online sales representative on Made in China or you may >>Click Here(for PC) or Click "Send Inquiry" at the bottom (for APP) to get quotes from Weshine.
The intuitive and user friendly diagnostic suite helps to improve measurement and data handling. It combines the control of the test system with data handling and basic evaluation options.
The PD-Mapping allows you to identify spots of increased PD activity depending on test voltage.
The software has a lot of functions, for example the ability to automatize testing procedures, which help to make the test even more comfortable.
Enhanced time domain reflectometry (TDR) options, including keyboard short-cut controls to increase evaluation speed.